Facility FAQ
Can’t find what you’re looking for? Call the PGE power protection experts at: 503-736-5750 or 800-270-7016 or contact us.

Q. One of the 200-amp circuit breakers that serve a compressor has tripped several times. An electrician was unable to find any overload problems with the circuit breaker and thought it was probably due to harmonics. What can be done to fix the problem?

Harmonics is a complex subject and when it causes circuit breakers to keep tripping, it’s a nuisance. Harmonic currents are caused by certain types of equipment that draw current intermittently while running. Harmonic currents flow from the load, through the circuit breaker, and into PGE’s system. If the circuit breaker is tripping because of harmonics, it may be defective, or you may require a different type of breaker that is not sensitive to harmonics.

Harmonics are sometimes blamed when a circuit breaker that is protecting a compressor trips. However, if a compressor is pulling more than 80 percent of its nameplate capacity for an extended period of time, it will, in fact, overload the breaker and trip. So a 200-amp circuit breaker should not have more than 160 amps per phase for any extended period of time.

Q. We have a small standby generator that supports our critical systems when we have a power outage. We also have small uninterruptible power supplies to support the loads until the generator starts. However, the UPS does not work correctly when the generator operates. Why not?

Not all UPS operate correctly when served by a generator. You can adjust the sensitivity of some UPS units so they work correctly with a small generator. Alternatively, it may be necessary to install better controls on the generator before the two can work together. Some generators do not have quality voltage and frequency regulation, while others cause too much voltage distortion. Each of these problems can cause some UPS systems to cycle their battery until it is depleted. Be sure to carefully review the specifications of any UPS you want to operate with a generator to ensure they will work together.

Q. We recently lost some control cards in one of our machines that has surge suppression. The repair technician told us the failure was due to surge damage. How can this be true?

Losing some control cards due to surge damage may indicate inadequate surge suppression or improper installation.

Another common cause of failure for control cards is inadequate or incorrect grounding of the control card system. Wiring errors can lead to failures even if surge protection is available. Call the PGE power protection experts for assistance at 503-736-5750 or 800-270-7016, or contact us.

Q. One of our large three-phase motors keeps tripping. An electrician told us the motor is not drawing the same amount of current on each phase and something must be wrong with the service from PGE. What can be done?

The PGE specification for voltage imbalance measured at your main service is 3 percent or less. Generally, we are below 2 percent. If the voltage is imbalanced it causes current imbalance in three-phase loads. And if there isn’t an equal load on each phase, the voltage imbalance can increase at different locations within your facility. If you think the voltage imbalance is higher than it should be, call the PGE power protection experts at 503-736-5750 or 800-270-7016, or contact us and ask us to measure your voltage.

Q. We have several variable frequency drives that frequently trip during the week. This usually occurs between 5 and 6 a.m. Do you know why this is occurring and what we can do to prevent it?

If a VFD trips early in the morning, it may be that it is sensitive to capacitor switching transients. PGE turns the capacitor banks on and off at the substations to support our customer load requirements. Some brands of drives (15 HP and smaller) are sensitive to this one cycle disturbance; newer, larger drives are not as susceptible. The most cost-effective way to reduce this type of nuisance tripping is to install line reactors.

Q. Every time a fault occurs our variable frequency drives trip off line. What can be done to prevent this from occurring?

Most faults are single-phase event, and most VFDs can ride through single-phase sags even when the voltage drops to almost zero. Unfortunately, the drive’s control circuit may not be able to handle such an event; a minor voltage sag on the control circuit can cause shutdown. There are many ways to solve this problem, but the two most cost-effective solutions are: 1) support the control circuit with an uninterruptible power supply, and 2) replace “weak link” control components with components that are less sensitive to sags. This may involve replacing only a few “ice cube” relays. To find out more, call the PGE power protection experts at 503-736-5750 or 800-270-7016 or contact us.

Q. We added variable frequency drives to some of our motors. Now they seem to be failing much sooner than expected. Can you explain this?

Adding VFDs to your existing motors is a good way to reduce your energy usage and have better control of your motors. However, it can lead to early failure of motors that are not designed to operate from a VFD. An inverter rated motor is one that is designed to operate correctly with a VFD. Motors that are not rated for use with a VFD can still be used with a drive, but additional mitigation steps are necessary to prevent early failure of the motor. To learn more, call the PGE power protection experts at 503-736-5750 or 800-270-7016 or contact us.

Back to top

Facility concerns
Different types of large commercial and industrial facilities face similar power quality problems. Here are 10 of the most common concerns:
  1. Grounding sensitive machinery
    Some equipment manufacturers specify that the power grounding system should not be used for sensitive machinery, such as computer numerical control machines. In fact, some CNC manufacturers designate the installation of a ground rod, separate from the power grounding electrode system, to serve as their ground reference. This type of installation, however, is a violation of the National Electric Code and under certain conditions can lead to personal injury and equipment damage.
  2. Accommodating large motor loads
    Starting a motor can require so much electricity that it reduces the voltage for all the other loads that share the same transformer. This can cause many problems, including control systems malfunctioning, high intensity discharge lighting failures and dimming lights. You can reduce the motor load by using soft start controllers and adjustable frequency drives.
  3. Correct installation of adjustable speed drives
    If you install adjustable speed drives, it’s likely you’ll experience nuisance trips and increase harmonic distortion unless you install line reactors or isolation transformers at the same time.
  4. Avoiding electrical noise
    Arcing loads, such as welders and electronic lighting, can create electrical noise that affects TVs, radios and telecommunications equipment. Enhanced grounding and bonding can increase the immunity to electrical noise.
  5. Dealing with older adjustable speed drives
    Older adjustable speed drives are often sensitive to minor power disturbances. Some newer drives feature stronger immunity capabilities. Call the PGE power protection experts about the installation of a new drive at 503-736-5750 or 800-270-7016. We can share important steps in specifying new drive performance criteria to minimize your power quality problems.
  6. Power factor correction
    You may create rather than diminish power quality problems when you combine power factor correction with harmonics-producing loads. Call the PGE power protection experts at 503-736-5750 or 800-270-7016 or contact us to find out more.
  7. Using neutral conductors
    Shared neutral conductors often lead to power quality problems. For example, if three branch circuits share one neutral conductor, the conductor could be overloaded. You can minimize problems by reducing load and using separate neutral conductors for each circuit.
  8. Serving sensitive equipment
    Large facilities often use long branch circuits to serve sensitive equipment locations. But, even with minor loads that cycle on and off, this can cause equipment to malfunction. To increase reliability, install a transformer near all sensitive equipment locations.
  9. Increasing UPS reliability
    If you use a UPS system to protect critical loads from power disturbances, make sure the battery string is good. Install battery monitoring systems and provide proper maintenance to increase the reliability of UPS systems.
  10. Ensuring generator reliability
    It is important to test your standby generator with building loads on a monthly basis to confirm that it is operating properly. By performing this type of regular testing, you can spot potential problems in advance and ensure that equipment will be in working order at critical times.